Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00610
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/29/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/11/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The listing data for the proposed hood calls for greater exhaust and supply air flow rates than provided by the proposed exhaust fan and make up air unit. Reference: Section 304.1, IMC 2018. [Initial comment: Provide mechanical specifications for the proposed Type I hood. Include all operating requirements and the weight for the hood. Reference: Section 107.2.1, IBC 2018.] |
04/11/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed |