Permit Number: T22CM00603
Parcel: 117033540

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00603
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/02/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00603
620 E University Bl – HR-3
Bedroom Addition (1st Review)

TRANSMITTAL: February 2, 2022
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HR-3 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6.

Historic review required for building addition within a HR-3 zone.

1. The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A).
As the actual perimeter yard setback was not provided from the proposed addition to the west property line Zoning cannot provide comments for the Historic Review. Based on a wall height of 14’-6” the required perimeter yard setback from the addition to the west property line is 9’-8”, proposes is unknown.

2. The zoning listed under Code Review is not correct and should be HR-3.

3. Under Code Review remove all references to “D.D.O” from the plan as a DDO has not been processed for this plan.

Historic review is required and must be approved prior to approval of this building plan. Historic application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/Preservation/HPZ_Review_Application_Package_2020.pdf, and is a separate submittal from the building plans submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using Submission Type “Historic Review”.



If you have any questions about this transmittal, please contact Elisa Hamblin at ElisaHamblin@tucsonaz.gov.
02/02/2022 SSHIELD1 ENGINEERING REVIEW Passed
02/02/2022 SSHIELD1 NPPO REVIEW Passed
02/08/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00603


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IRC Section R310. Revise drawings with emergency escape and rescue opening net clear dimension of window when fully open for bedroom #2 (verify existing window size).
2. 2018 IRC Section R806. Revise drawings with roof cross ventilation openings including minimum of 1-inch space between the insulation and roof sheathing or provide unvented enclosed rafter framing with air-permeable insulation (sheet S2.0 not provided per keynote A23).


MECHANICAL REVIEW COMMENTS:
Denied
1. 2018 IRC Section M1501.1 and M1504.3. Revise plans with every mechanical exhaust system discharge to the outdoors and not into an attic, soffit, ridge vent or crawl space (toilet exhausts & clothes dryer).
2. 2018 IRC Section M1502.3. Revise plans with clothes dryer exhaust termination on the outside of the building and not less than 3 feet from any openings.
3. 2018 IRC Section M1502.4.1 and M1502.4.2. Revise plans with clothes dryer exhaust duct details including type of metal, thickness and joints cannot have screws or fasteners that protrude more than 1/8 inch into the inside of duct.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved