Permit Number: T22CM00579
Parcel: 127111700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00579
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/07/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV-0; Design Specification: The Construction indicates a single family residence (SFR). If this is an apartment building with 3 or more units, it would be considered a commercial project (R-2 Occupancy Classification). Please verify and revise the drawing as required.
2. Sheet PV-0; Applicable Codes: If this is an apartment building with 3 or more units, it would be considered a commercial project. Please verify and revise the applicable codes to the 2018 IBC and 2018 IFC.
3. Sheet PV-3: A note on this sheet indicates "Meets or exceeds IBC IRC construction standards load calculations". An analysis by a registered structural engineer should be provided to determine if the existing roof structure is capable of supporting the new loads from the PV system. Provide calculations, plans, and details sealed, signed, and dated by the engineer.
4. General: Please provide written responses to all review comments.
02/17/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. This is a commercial project, requiring all documents to be prepared, sealed, signed, and dated by a registered Electrical design professional. Provide complete electrical plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements
03/02/2022 IMONSHI1 ZONING REVIEW Approved
03/02/2022 IMONSHI1 ENGINEERING REVIEW Passed