Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00497
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00497 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved Approved/ Subject to field approval ELECTRICAL REVIEW COMMENTS Conditionally Approved PLUMBING REVIEW COMMENTS: Denied Second Review: 1-3 OK 4). Now that the gas sizing table 402.4 (3) has been added to plan page P-601 the 1" gas line on pages P-12 & P502 is undersized for this systems total distance & should be 1.25" 5). Now that the grease interceptor & DFU load info has been provided on plan page P-601 the grease interceptor is undersized & should be 1500 gallon unit. -Per Tucson Plumbing Amendments Grease interceptor sizing table 6). OK 7). SAME- Condensate & Ice Machine shown on P-101 can't discharge to the grease system. -IPC 1003.2 ** Fridge, & Freezer condensate still connecting to Grease System ** 8-11 OK If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |