04/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00497

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/ Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1-3 OK
4). Now that the gas sizing table 402.4 (3) has been added to plan page P-601 the 1" gas line on pages P-12 & P502 is undersized for this systems total distance & should be 1.25"
5). Now that the grease interceptor & DFU load info has been provided on plan page P-601 the grease interceptor is undersized & should be 1500 gallon unit. -Per Tucson Plumbing Amendments Grease interceptor sizing table
6). OK
7). SAME- Condensate & Ice Machine shown on P-101 can't discharge to the grease system. -IPC 1003.2 ** Fridge, & Freezer condensate still connecting to Grease System **
8-11 OK