Permit Number: T22CM00484
Parcel: 133291300

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00484
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2022 SSHIELD1 ENGINEERING REVIEW Passed
02/02/2022 STEVE SHIELDS ZONING REVIEW Approved
02/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00484


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Denied
1. 2018 IRC Section R106.1.1. Revise construction documents by removing all references to 2012 International Residential Code on Sheet 2 Foundation Plan (3 location).
2. 2018 IRC Section R314.2.2, R314.3 and R314.4. Revise Sheet 7 Electrical Plan noting smoke detectors are to be interconnected in such a manner that the actuation of one alarm will activate all of the alarms in the individual dwelling unit.
3. 2018 IRC Section 315.2.2 and R315.3. Revise drawings with location of carbon monoxide alarm outside of the new bedroom.


MECHANICAL REVIEW COMMENTS:
Denied
1. 2018 IRC Section M1501.1 and M1504.3. Revise plans with every mechanical exhaust system discharge to the outdoors and not into an attic, soffit, ridge vent or crawl space.
2. 2018 IRC Section M1502.3. Revise plans with clothes dryer exhaust termination on the outside of the building and not less than 3 feet from any openings.
3. 2018 IRC Section M1502.4.1 and M1502.4.2. Revise plans with clothes dryer exhaust duct details including type of metal, thickness and joints cannot have screws or fasteners that protrude more than 1/8 inch into the inside of duct.

ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Approved