Permit Number: T22CM00469
Parcel: 12007342A

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00469
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00469
373 W President St. - R-2
Detached Garage Addition. (1st Review)

TRANSMITTAL: January 27, 2022

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, to include but not limited to:
a. Provide the owners name on the plot plan.
b. Provide a lot coverage calculation on the plot plan.
c. Show the location of all utilities on the plot plan.
d. Provide the zoning for all adjacent parcels.
e. Provide the legal description on the plot plan.
f. Provide the property dimensions on the plot plan. The deminions provided on the plan for both the north/south and east/west property lines appear to exceed the property boundries.

2. Provide a building height dimension from design grade to the mid-point of the pitched roof see UDC Article 6.4.4.A. This dimension will be used to verify that the proposed shed does not exceed the allowed 12’ height for a detached accessory structure, see UDC Article 6.6.3.C.

3. The neighbor’s setback waive is required to be on the plot plan not a separate sheet.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
01/27/2022 SSHIELD1 ENGINEERING REVIEW Passed
01/27/2022 SSHIELD1 NPPO REVIEW Passed
02/11/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00469

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
Need to show the foundation design and section meeting the requirements of Section R403


BUILDING REVIEW COMMENTS:
Denied
Need to show the foundation design and section meeting the requirements of Section R403


MECHANICAL REVIEW COMMENTS:
Approved
No mechanical equipment shown being installed.


ELECTRICAL REVIEW COMMENTS
Denied
Need to show the electrical equipment and wiring size and design.


PLUMBING REVIEW COMMENTS:
Approved