Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00422
Parcel: 13409018F

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM00422
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2022 ROBERT SHERRY WATER REVIEW Completed
02/22/2022 LSHAMIS1 ZONING REVIEW Approved
02/24/2022 JVINCEN1 FIRE REVIEW Approved
03/02/2022 LSHAMIS1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
03/17/2022 SBLOOD1 ENGINEERING REVIEW Approved
04/11/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00422


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. The Architectural Drawing A4 shows two RTU’s. One is a New Roof Top Unit at Line 4 between Lines A and B and the second is New Roof Condenser Unit at 5 between C and D. The Structural Drawing S1 show one RCU at line 5 between Line A and B. The Mechanical Drawing M1 show one RTU between A & B and 2 & 3. Verify and submit the response by addressing the inconsistency.
2. Provide Structural Calculations for the adequacy of existing roof to support both New RTU’s.
3. All Calculations shall be sealed and signed by Professional Engineer registered with State of Arizona per Section 107.1 of International Building Code 2018.
Submit a response letter addressing these correction items and provide bubbles on the revisions to the drawings.


BUILDING REVIEW COMMENTS:
Denied
1. Provide the full specification manual.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
E1 LIGHTING PLAN: Hexagon numbers have no reference note to call out as fixture type.
E4.1 PANELBOARD SCHEDULES: Load calculations indicate that the client may need to upsize relocated UPS as calculations indicate that it may be overloaded.


PLUMBING REVIEW COMMENTS:
Conditionally Approved
First Plumbing Review:
1). Roof Level Condensate receptor on plan page P1 will need to be protected from receiving storm water. -IPC 1101.3 (Field Verify)
2). Floor drains on plan page P2 will need trap primers -IPC 1002.4.1 ( Field Verify)


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
04/12/2022 VVERA1 OUT TO CUSTOMER Completed