Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00420
Parcel: 11304148A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM00420
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2022 ROBERT SHERRY WATER REVIEW Completed
02/14/2022 NMARTEL1 ZONING REVIEW Approved
02/14/2022 NMARTEL1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/17/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00420


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide the specifications manual that provides the schedule of special inspections.


BUILDING REVIEW COMMENTS:
Denied
1. Provide the specifications manual that provides the schedule of special inspections.


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/subject to field approval


ELECTRICAL REVIEW COMMENTS
Approved
E1 LIGHTING PLAN: Should normally provide a Comcheck.


PLUMBING REVIEW COMMENTS:
Denied
1). Add ASSE 1022 or 1024 backflow preventer to plan page P1.1 for the coffee maker shown plan Page BR1... -IPC 608.17.1.2


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
03/02/2022 JPEELDA1 FIRE REVIEW Approved
03/17/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change This project is within a mapped flood hazard area and requires a Floodplain Use Permit (FUP.)
Please start a new FUP at our permit application web page: https://docs.tucsonaz.gov/Forms/tucsonpermitapp.
Instructions:
1. Is this for a new or existing activity application? - Please select New Application.

2. Submission Type - Select Floodplain Use Permit.

3. Project Name - Enter a name for your project.

4. Type of Permit - Select Commercial or Residential (Residential is for work on single family residences and duplexes.)

5. Select Street Name from the list. You can type the first two letters or number to get closer to your choice in the list. Then select the rest of the address in the boxes provided.

6. Description of Work - Enter in Floodplain Use Permit for…and then put a description of the work being done or reference the building permit number associated with this floodplain use permit.

7. Complete the Applicant Info. (Note APA# is for applicants with an advance payment account. Leave blank is you do not have an APA account.

8. Complete the Contractor, Owner and Architect/Engineer sections as applicable.

9. Supporting Documentation Upload - Provide a complete cost estimate for the project unless it is for a new build/separate structure. You may also provide additional documents you think will be helpful.

10. Sign the application and submit.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
03/18/2022 VVERA1 OUT TO CUSTOMER Completed