Permit Number: T22CM00411
Parcel: 12419025A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00411
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/26/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Appliances (e.g. beverage dispensers, ice makers, etc.) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.14.1, IPC 2018 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1, 608.3, and 608.17.1.2, IPC 2018.
2. Verify that the Pima County Regional Wastewater Reclamation Department (Contact: steven.valencia@pima gov) will not require the installation of a grease interceptor for the fresh food preparation area. Reference: Section 1003.3, IPC 2018, as amended by the City of Tucson.
01/26/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide general room exhaust for any cooking appliance that does not require the installation of a Type II hood (e.g. electric oven, microwave, etc.). The minimum exhaust rate shall be 0.70 CFM per square foot, using a minimum area of 100 square feet for each individual appliance. Reference: Section 507.1, exception 2 and 507.3, IMC 2018.
01/26/2022 ROBERT SHERRY WATER REVIEW Completed
02/01/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/10/2022 IMONSHI1 ZONING REVIEW Approved
02/10/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
03/02/2022 JPEELDA1 FIRE REVIEW Approved