Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00402
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/03/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T22CM00402 & T22CM00401 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: N/A BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Conditionally Approved Approved/Subject to field approval ELECTRICAL REVIEW COMMENTS Conditionally Approved Comcheck submitted as separate document, no issues. EP2.1 POWER FLOOR PLAN: Has inappropriate Keynotes on the Main Floor plan. E5.1 ELECTRICAL RISER DIAGRAM & SCHEDULE: Calculated Fault for F003 is calculated to low, but actual Fault at F003 is still below 10 KAIC and does not affect design. E7.1 ELECTRICAL DETAILS: Trench depth for Electric service 12 inches deeper than required (36 inch depth is acceptable). PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |
| 06/21/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 07/21/2022 | SBLOOD1 | ENGINEERING | REVIEW | Approved |