Permit Number: T22CM00402
Parcel: 111073140

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00402
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM00402 & T22CM00401

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved

Comcheck submitted as separate document, no issues.
EP2.1 POWER FLOOR PLAN: Has inappropriate Keynotes on the Main Floor plan.
E5.1 ELECTRICAL RISER DIAGRAM & SCHEDULE: Calculated Fault for F003 is calculated to low, but actual Fault at F003 is still below 10 KAIC and does not affect design.
E7.1 ELECTRICAL DETAILS: Trench depth for Electric service 12 inches deeper than required (36 inch depth is acceptable).


PLUMBING REVIEW COMMENTS:
Approved


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
06/21/2022 STEVE SHIELDS ZONING REVIEW Approved
07/21/2022 SBLOOD1 ENGINEERING REVIEW Approved