Permit Number: T22CM00402
Parcel: 111073140

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00402
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2022 ROBERT SHERRY WATER REVIEW Completed
03/24/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING CANNOT APPROVE PLANS UNTIL DP21-0298 IS APPROVED.
03/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00402 & T22CM00401

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
N/A


BUILDING REVIEW COMMENTS:
Conditionally Approved
1. Remove sheets T1.1 and T1.2 that do not have the corrected revisions


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
1. All violations complied
2. Approved/Subject to field approva


ELECTRICAL REVIEW COMMENTS
Conditionally Approved
Approved with the following comments
EP2.1 POWER FLOOR PLAN: Riser Room detail calls out to be shown on sheet EP4.1, but is actually shown on this sheet.
E5.1 ELECTRICAL RISER DIAGRAM & SCHEDULE: Provide conductor sizes and short circuit calculations for each panel. Relocated panels require new calculations as distances and feeders affect these values and this is a Tucson City requirement.
EOR response: Existing 120/240V/1PH electrical service to be replaced with new 277/480V/3PH service. Refer to sheet E6.1 for new schedules and E5.1 for revised riser diagrams. Refer to Feeders and Services Schedules on sheet E5.1 for calculations. Refer to sheet E1.1 for locations of services being removed and added.
2nd Review Response by Reviewer (sheet completely redone): F003 calculation seems low, should re-calculate to confirm. However infinite bus calculation would still be below 10 KAIC rating of panel,.


PLUMBING REVIEW COMMENTS:
Denied
Second Review:
1-3 OK
4). SAME-Plan pages A2.9 roof details, & Plumbing demo pages PD 2.1, PD3.1, &PD3.2 are missing? -IPC A106.3.1
5-7 OK GAS Work Removed
8). OK
9). SAME-Site utility piping plan C6.0 Bldg. Fire, water, sewer and storm connections don't correlate with plan pg P2.1. -IPC A106.3.1
10). SAME-Key note #6 Storm drain, needs to illustrate the routing, sizing, and connection point information on P2.1 & C6.0. -IPC A106.3.1


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/05/2022 JPEELDA1 FIRE REVIEW Approved
04/05/2022 JGARCIA1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/15/2022 DBENOIT1 ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/15/2022 DBENOIT1 APPROVAL SHELF Completed
04/15/2022 DBENOIT1 OUT TO CUSTOMER Completed
04/15/2022 DBENOIT1 REJECT SHELF Completed