Permit Number: T22CM00400
Parcel: 134180030

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00400
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/30/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Correct the arithmetic shown in the ventilation calculations. As single-zone areas, 3306 square feet of retail sales space requires 961 CFM of outside air, 1494 square feet of retail storage requires 224 CFM of outside air. [Second comment: Comment not resolved. Show the locations of the supply and return devices on the reflected ceiling plan.] [Initial comment: Show that adequate ventilation (e.g. HVAC supply/returns) is being provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.]
04/05/2022 JPEELDA1 FIRE REVIEW Approved