Permit Number: T22CM00400
Parcel: 134180030

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00400
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet C1; Code Review: The occupant load indicates 243 total occupants for a B occupancy classification, and the Restroom Requirements indicate this meets the IBC Section 2902.1. Per the IBC Table 2902.1, two restrooms is not adequate for that occupant load. Please verify and revise as required.
2. Sheet C1; Accessible Path of Travel Plan: Please indicate the exit access travel distance on this plan, and verify the distances meet the requirements of the IBC Table 1017.2. Indicate this information in the Code Review section of Sheet C1.
3. Sheet A2; Floor Plan: Please provide a detail and/or note at the Reception Counter to indicate the height of the service counter as 34" above finish floor.
4. Sheet A3; Typical Restroom Elevations: On the side wall elevation, please indicate and dimensionally locate the vertical grab bar per the ICC/ANSI Figure 604.5.1.
5. General: Is this a first tenant into a shell space? Please verify and indicate on Sheet C1.
6. General: Please provide written responses to all review comments.
01/26/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show that adequate ventilation (e.g. HVAC supply/returns) is being provided for the occupied spaces. Reference: Section 403.3.1.1, IMC 2018.
01/26/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
01/26/2022 ROBERT SHERRY WATER REVIEW Completed
02/08/2022 WBERGER1 ZONING REVIEW Approved
02/08/2022 WBERGER1 ENGINEERING REVIEW Passed
02/08/2022 WBERGER1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/15/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/02/2022 JPEELDA1 FIRE REVIEW Reqs Change Sheet C1; Accessible Path of Travel Plan: Please indicate the exit access travel distance on this plan, and verify the distances meet the requirements of the IBC Table 1017.2. Indicate this information in the Code Review section of Sheet C1.