Permit Number: T22CM00391
Parcel: 122080810

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00391
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2022 STEVE SHIELDS ZONING REVIEW Reqs Change FROM: PDSD Zoning Review

PROJECT:
T22CM00391
2138 N Sycamore Bl - R-1
Remodel 2nd Dwelling Unit (1st Review)

TRANSMITTAL: January 31, 2022

This site is located in the R-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. Provide a residential plot plan that meets the requirements of the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf.

2. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-1 Zone the minimum lot size for an R-1 zoned property to allow two (2) dwelling units is 10,000 sq. ft. Provide approved permit documents for this unit with your next submittal.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
01/31/2022 SBLOOD1 ENGINEERING REVIEW Reqs Change See zoning comments for need of a residential plot plan.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
02/09/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T22CM00391
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide an updated complete plan set with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet Zoning and other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments on 1/1/2019. Show the current code reference on the plans.

Consolidate pages of construction plans into a single .PDF file as prescribed at the PDSD web site.

Sample plans are available at https://www.tucsonaz.gov/pdsd/residential-permits

FLOOR PLANS:

1. Show a floor plan labeling all proposed functions of rooms and spaces, R106.1.1. Bedrooms have additional requirements from other living spaces.

PLUMBING PLANS:

1. Provide a plumbing plan showing fixture locations with appropriate separation, 2018 IRC R307.
2. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.

MECHANICAL PLANS:

1. Provide heating facilities (duct plan) for supplying conditioned air to all habitable rooms, R303.9.

ELECTRICAL PLANS:

1. Interior alterations require the installation of smoke alarms at existing bedrooms, R314.2.2. Smoke alarms are required outside each separate sleeping area, R314.3.2.
2. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
3. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
4. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms with GFCI protection) including receptacles, lights and smoke detectors require combination type arc-fault circuit interrupters, E3902.16.

If you have any questions, please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review