| 02/09/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T22CM00386 Rooftop Solar Panels (1st Review) 1729 E ALLEN RD TRANSMITTAL DATE: ?February ?9, ?2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments COMMENT: After researching PRO there are records for an expired SFR T04CM05062, there are outstanding inspections. In order to place the solar panel on this SFR, a "Finals only permit" will have to be obtained and the permit referenced above must be finalized. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by phone (520)837-4986 or email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |