Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T22CM00386
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2022 | PCAMARE1 | OIP | REVIEW | Reqs Change | FROM: Paul Camarena PDSD Residential Review Section PROJECT: T22CM00386 Rooftop Solar Panels (1st Review) 1729 E ALLEN RD TRANSMITTAL DATE: ?February ?9, ?2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed. COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments COMMENT: After researching PRO there are records for an expired SFR T04CM05062, there are outstanding inspections. In order to place the solar panel on this SFR, a "Finals only permit" will have to be obtained and the permit referenced above must be finalized. COMMENT: Residential will review the application on the next submittal If you have any questions about this transmittal, Contact Paul Camarena any time during the week by phone (520)837-4986 or email Paul.camarena@tucsonaz.gov RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/09/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |