Permit Number: T22CM00383
Parcel: 14117007Q

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM00383
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2022 ROBERT SHERRY WATER REVIEW Completed
02/02/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00383


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved

BUILDING REVIEW COMMENTS:
Denied
1. Sheet TS1:The construction type listed is not a recognized construction type. It is listed as A.5. Provide a corrected construction type and correlate any applicable requirements.
2. Provide exiting hardware for the fence gate as it is part of the egress system. Section 1010.2.
3. At least 5% of the seating is required to be accessible and be dispersed among all seating types , including the bar area, in accordance with Section 226.1 2010 ADAAG

MECHANICAL REVIEW COMMENTS:
Denied
1. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
1. Provide all gas load calculations.
2. No plumbing details provided. Provide all applicable plumbing details.
02/09/2022 IMONSHI1 ENGINEERING REVIEW Passed
02/09/2022 IMONSHI1 ZONING REVIEW Approved
02/09/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
03/02/2022 JPEELDA1 FIRE REVIEW Reqs Change REVIEW COMMENTS:
Denied
1. Sheet TS1:The construction type listed is not a recognized construction type. It is listed as A.5. Provide a corrected construction type and correlate any applicable requirements.
2. Provide exiting hardware for the fence gate as it is part of the egress system. Section 1010.2.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2022 NGARCIA3 OUT TO CUSTOMER Completed