Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00366
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2022 | DBENOIT1 | 2ND PARTY REVIEW | REVIEW | Approv-Cond | Activity Number: T22CM00366 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Conditionally Approved Reference Building and Energy and Structural Comments and Responses/Revisions: Though the insulation scheme has been changed in accordance with prior comment, Sheet A107 Section “A” still shows that the area above the porch ceiling and above the living area are interconnected. Since the roof insulation for the living area is against the roof decking, not in the ceiling space, the thermal envelope is discontinuous. The insulated exterior wall should either be extended to the insulated roof deck, or the roof-ceiling insulation should be at the ceiling level. If the ceiling is insulated, the attic space will need to be ventilated in accordance with IRC Section R806.5, unless any of the exceptions apply. BUILDING REVIEW COMMENTS: Conditionally Approved Sheet A-107 Section "A": Insulation has been provided at the ceiling level per prior comment. Please note that the proposed batt insulation must be a minimum of R-38; however, if the insulation is extended uncompressed over the top plates of the exterior walls, the specified R-30 may be used (IECC Section R402.2) Sheet A-107 Section "A" (and others): Gable vents of unspecified size have been added to address the need to ventilate the attic upon movement of the attic insulation to the ceiling level. Please note that IRC Section R806.2 requires that the minimum net ventilating area under these conditions is 1/150 of the area of the vented space. MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Conditionally Approved See comments regarding smoke and Carbon Monoxide alarms on Building Plan review. PLUMBING REVIEW COMMENTS: Approved If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov |