Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00361
Parcel: 116150810

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T22CM00361
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00361


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide all special inspection information along with the statement of special inspections in compliance with Chapter 17.

BUILDING REVIEW COMMENTS:
Denied
1. Provide a new thorough egress plan.
2. Provide clarification on the separation between the business portion and the residential portion of the building. Provide evidence of compliance in accordance with Section 508.
3. The occupant load is calculated incorrectly. There are many spaces in the residential portion that are not accounted for within the calculation. Section 1004.3 and Table 1004.5
4. Depending on the separation required in regards with comment #2, door #108 is required to comply with Section 716 and Table 716.1(2).

MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved

PLUMBING REVIEW COMMENTS:
Approved
01/27/2022 ROBERT SHERRY WATER REVIEW Completed
02/08/2022 SBLOOD1 ENGINEERING REVIEW Passed
02/09/2022 IMONSHI1 ZONING REVIEW Approved
02/09/2022 IMONSHI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
03/02/2022 JPEELDA1 FIRE REVIEW Reqs Change REVIEW COMMENTS:
Denied
1. Provide a new thorough egress plan.
2. Provide clarification on the separation between the business portion and the residential portion of the building. Provide evidence of compliance in accordance with Section 508.
3. The occupant load is calculated incorrectly. There are many spaces in the residential portion that are not accounted for within the calculation. Section 1004.3 and Table 1004.5
4. Depending on the separation required in regards with comment #2, door #108 is required to comply with Section 716 and Table 716.1(2).
5. Sheet G1 shows that the occupancy type is a R-1 and it is actually a R-4 and or a I-2 Condition 1 please clarify.
6. Provide detail showing that the separation from B and others meets the requirements of 716 IBC, 2018
7. Fire alarm shall show as a deferred submittal to TFD
8. Owner to obtain a State Licensed Facility operational permit from TFD

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
03/02/2022 NGARCIA3 OUT TO CUSTOMER Completed