Review Date Reviewer's Name Type of Review Description Status Comments
06/06/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Standard detail RWRD 401 allows the use of either a wye fitting or a machine-cut tapping saddle. For a private sewer, the IPC is the controlling document. Section 707.1, IPC 2018, prohibits the use of saddle-type fittings: revise keynote 8 on sheet 3 of 9 to indicate that directional fitting will be required. [Initial comment: The use of saddle-type fittings to connect to a private sewer is prohibited, use directional wye fittings to connect the building sewers to the sewer main. Reference: Section 707.1 (6), IPC 2018 and Detail RWRD 401.]