Permit Number: T22CM00317
Parcel: 11452008G

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00317
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/03/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change The use of saddle-type fittings to connect to a private sewer is prohibited, use directional wye fittings to connect the building sewers to the sewer main. Reference: Section 707.1 (6), IPC 2018 and Detail RWRD 401.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/03/2022 NGARCIA3 OUT TO CUSTOMER Completed