Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T22CM00315
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 01/20/2022 | VFLORES1 | COMMUNICATIONS | REVIEW | Approved | |
| 01/31/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/03/2022 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 02/09/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . The electrical line diagram shows a existing service disconnect. The note in bold lettering indicates to install a 200 amp circuit breaker to match AIC rating as the existing breakers.What existing circuit breakers? For clarity, indicate the type the main service disconnect is going to be. Fused disconnect or enclosure with a Main Breaker. And include the AIC rating. 2. Indicate the conduit, conductor sizes and types between the meter and the service disconnect. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
| 03/01/2022 | LSHAMIS1 | ZONING | REVIEW | Completed | CDRC Transmittal FROM: Loran Shamis PDSD Zoning Review Section PROJECT: T22CM00315 Collocation of antennas, ancillary and ground equipment (1st Review) 1010 S Wilmont Rd TRANSMITTAL DATE: February 17, 2022 DUE DATE: February 14, 2022 COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed. The proposed use is wireless communications and the site is zoned C-2. The proposed use is granted through a PDSD Special Exception Procedure, reference T21SE00047. 01. COMMENT: As you are proposing improvements to a commercial site, an updated Development Package is required (UDC, 3.3.3). See Checklist for Minor Changes to an Existing Commercial Site - https://www.tucsonaz.gov/files/pdsd/forms/Minor_Changes_to_Commercial_Industrial_Sites_.pdf For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp |
| 03/01/2022 | PETER MCLAUGHLIN | PLANNING-CITY HALL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/01/2022 | VVERA1 | OUT TO CUSTOMER | Completed |