Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00306
Parcel: 12218381A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T22CM00306
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . The comment response letter states, "The 3-meter pack feeds 3 units.... 3503-2, 3505, 3507". The line diagram correlates with this. However, the site plan shows 3501, 3503, 3505 ½, 3505, 3507. Where is 3503-2? Also correlate the load calculations with the correct units and include the 60- amp sub- panels in the load calculations.

2. The total load calculation shown exceeds the rating of the service equipment. Please revise as necessary.

3. Show the location of the new 125-amp sub- panels and the existing 60-amp sub- panels on the plan.

4. If the branch circuits are modified as described in NEC art 210.12.D, provide the branch circuit protection required.

Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/09/2022 NGARCIA3 OUT TO CUSTOMER Completed