05/09/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . The comment response letter states, "The 3-meter pack feeds 3 units.... 3503-2, 3505, 3507". The line diagram correlates with this. However, the site plan shows 3501, 3503, 3505 ½, 3505, 3507. Where is 3503-2? Also correlate the load calculations with the correct units and include the 60- amp sub- panels in the load calculations. 2. The total load calculation shown exceeds the rating of the service equipment. Please revise as necessary. 3. Show the location of the new 125-amp sub- panels and the existing 60-amp sub- panels on the plan. 4. If the branch circuits are modified as described in NEC art 210.12.D, provide the branch circuit protection required. Ref; 2018 IBC sec 107.2.1, 2017 NEC, 2018 IECC, City of Tucson Commercial Plan Submittal Requirements. |