03/03/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change The line diagram is incomplete. Previous review comment,

“2. Provide a complete electrical line diagram. Include all conduit, conductor sizes and types, AiC, voltage, phase, and amp rating, OCPD’s, etc. “

Show Riser conduit and conductor sizes and types.

Feeder conduits and or cable types.

Voltage, Phase, AIC rating of equipment and available fault current at the service per TEP.

Justify the increase in amp rating for the new service. If the load is increasing, provide load calculations.

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.