Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00306
Parcel: 12218381A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T22CM00306
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/09/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the electrical plan review comments and provide a written response.

1 . Provide a site plan showing the location of the relocated electrical service on the building.

2. Provide a complete electrical line diagram. Include all conduit, conductor sizes and types, AiC, voltage, phase, and amp rating, OCPD’s, etc.

3. What size is the existing electrical service?

Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2022 NGARCIA3 OUT TO CUSTOMER Completed