Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T22CM00306
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Provide a site plan showing the location of the relocated electrical service on the building. 2. Provide a complete electrical line diagram. Include all conduit, conductor sizes and types, AiC, voltage, phase, and amp rating, OCPD’s, etc. 3. What size is the existing electrical service? Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/09/2022 | NGARCIA3 | OUT TO CUSTOMER | Completed |