Permit Number: T22CM00296
Parcel: 11714298B

Address:
500 S CONVENT AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00296
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2022 AWARNER1 NPPO REVIEW Passed
01/21/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/27/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00296
500 S Convent Ave – HO-3
Rear Porch (1st Review)

TRANSMITTAL: January 27, 2022
COMMENTS: the following comments are relative to an application for Historic Review (UDC 5.8.8).

This site is located in the HO-3 zone (UDC 4.7.15). A single-family residence is a permitted use in this zone (Table 4.8-3).

Historic review can waive required perimeter yard setbacks.

Historic review is required and must be approved prior to approval of this building plan. Historic application/requirements can be found at: https://www.tucsonaz.gov/files/pdsd/Preservation/HPZ_Review_Application_Package_2020.pdf, and is a separate submittal from the building plans submitted at: https://www.tucsonaz.gov/pdsd-filedrop, using Submission Type “Historic Review”.

The minimum setback is the greater of ten (10) feet, or three-quarters (3/4) the height of the structure’s wall facing each interior property line (Table 6.3-3.A).

1. Required perimeter yard setback from the proposed porch to the north & south property line is 10’-0”, proposed setback was not provided. Per UDC Article 6.4.5.B.2 the setback for a porch type structure is measured from the vertical structural member(s) (i.e., post, column, dormer wall) supporting a roof extension from the principal structure.

2. Based on the provided plan it appears that you are proposing an encroachment into the neighbors yard to the north. Some type of recorded easement or agreement is required for this encroachment.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
02/08/2022 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change Show ledger anchor size and spacing for deck to foundation, R507.9.

A special inspection request is required with the permit plans for epoxy sets and field welding, R109.2.