Permit Number: T22CM00282
Parcel: 136328110

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00282
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed Activity Number: T22CM00282

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Conditionally Approved
See comments under main building permit. This permit is approved subject to those comments.


BUILDING REVIEW COMMENTS:
Conditionally Approved
2018 IRC Section R315.2 and R315: Carbon monoxide alarm/smoke detector has been added/located within the garage in the vicinity of the entrance to the existing office in the main house. As per prior comment, the CO alarm/detector must be located outside of each sleeping area in the immediate vicinity of the bedrooms. Smoke detector/alarms must be similarly located, and one must also be installed in each sleeping room. The comment requested clarification of the existing conditions in this regard. None need be added if the home is in compliance. Location of either alarm within the garage proper could result in false alarms. It is also questionable if there is a need for same in the vicinity of the office, unless it will double as a sleeping room. It is recommended that existing on-site conditions be confirmed with the authority having jurisdiction (AHJ), and the need for/location of such alarms be determined at that time.
Please not that "AHJ" refers to "Authority Having Jurisdiction", in this case the City of Tucson Building Official.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
No plumbing indicated in scope work or on plans.


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov