Permit Number: T22CM00282
Parcel: 136328110

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00282
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/26/2022 STEVE SHIELDS ZONING REVIEW Approved
02/08/2022 SBLOOD1 ENGINEERING REVIEW Approved
02/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00282

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
See comments under general building permit.


BUILDING REVIEW COMMENTS:
Denied
2018 IRC Section 315.2 and R315.3. Revise drawings with location of carbon monoxide alarm outside of the bedroom(s), when the dwelling unit includes a fuel-fired appliance and/or has an attached garage (confirm new installation or compliant pre-existing installation).
2018 IRC Section R403.1.4. Revise drawings with exterior footings at least 12 inches below undisturbed ground surface. Current drawings allow the option of footing termination upon reaching "firm soil".
2018 IRC Section R403.1.6. Revise drawings with anchor bolts at maximum of 6 feet on center and no fewer than two bolts per plate section for wood sole plates and sill plates on concrete floor slab, concrete, and masonry foundation/walls (other than braced wall sections).
2018 IRC Section R602.10. Revise drawings to reflect compliance with wall bracing requirements for the braced wall line encompassing the 10' garage door.
DEFERRED SUBMITTALS REQUIRED:
Shop drawings, including layout and individual component design diagrams for roof-ceiling framing, including glued laminate timber beams and Truss Joist components. Provide to AHJ prior to inspection.


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Approved


PLUMBING REVIEW COMMENTS:
Denied
No plumbing indicated in scope of work/construction documents.