Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM00271
Parcel: 11105153C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00271
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed
08/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00271 – DP21-0301
3430 E Presidio Rd – Unit 1102. - R-2
New Building – Multi-Family (2nd Review)

TRANSMITTAL: August 9, 2022

This site is located in the R-2 zone (UDC 4.7.9). A multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Zoning has reviewed the building plan for compliance with DP21-0301 and although the plans appear to match Zoning cannot approve the building plan until the DP is approved.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/16/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans show that you are installing a NFPA 13D Fire sprinkler and installing a fire alarm system. Occupancy is stated to be a R-3 then a fire alarm is not required. Please correct the plans.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
09/02/2022 SBLOOD1 ENGINEERING REVIEW Approved