Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00271


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Denied
1. Provide the statement of special inspections.

BUILDING REVIEW COMMENTS:
Denied
1. Provide clarification on the occupancy classification. R-2 occupancies are not permitted to be protected by an NFPA 13D system in accordance with Section 903.3.1.3. A one and two family dwelling is not an R-2 occupancy and thus would not be within the scope of the IBC. The plans more represent a R-2 occupancy apartment building. Provide clarification and correlate appropriate code requirements. This is an addition causing two 1/2 family dwellings to become an R-2 occupancy and would need to meet the requirements of the IBC.
2. The allowable stories calculation is incorrect in accordance with Table 504.4. R-2 occupancies protected by NFPA 13D are not permitted.
3. The allowable square footage calculation is incorrect in accordance with Table 506.2. R-2 occupancies protected by NFPA 13D are not permitted.
4. Provide occupant loads.
5. Provide a thorough egress plan.
6. The shared partition walls of the units are to be compliant with Section 420 of the IBC.
7. Additional comments may apply once comment #1 is addressed.
MECHANICAL REVIEW COMMENTS:
Denied
1. The dryer exhausts within 3 feet of operable buildings. Provide a dryer exhaust that is in accordance with Section 501.3.1 #3.
2. Clothes dryer exhausts exhausting more than 200 cfm is required to have makeup air. Provide clarification in accordance with Section 504.6.
3. The plans indicate an EF-3, however no information is provided on the schedule. Provide the appropriate information.
4. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.

ELECTRICAL REVIEW COMMENTS
Denied
1. Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance.
2. Provide a one line diagram.

PLUMBING REVIEW COMMENTS:
Approved
01/27/2022 ROBERT SHERRY WATER REVIEW Passed
02/03/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/03/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00271 – DP21-0301
3430 E Presidio Rd – Unit 1102. - R-2
New Building – Multi-Family (1st Review)

TRANSMITTAL: February 3, 2022

This site is located in the R-2 zone (UDC 4.7.9). A multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Zoning has reviewed the building plan for compliance with DP21-0301 and although the plans appear to match Zoning cannot approve the building plan until the DP is approved.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
02/03/2022 SSHIELD1 ENGINEERING REVIEW Needs Review
02/25/2022 JPEELDA1 FIRE REVIEW Reqs Change Denied
1. Provide clarification on the occupancy classification. R-2 occupancies are not permitted to be protected by an NFPA 13D system in accordance with Section 903.3.1.3. A one and two family dwelling is not an R-2 occupancy and thus would not be within the scope of the IBC. Provide clarification and correlate appropriate code requirements.
2. The allowable stories calculation is incorrect in accordance with Table 504.4. R-2 occupancies protected by NFPA 13D are not permitted.
3. The allowable square footage calculation is incorrect in accordance with Table 506.2. R-2 occupancies protected by NFPA 13D are not permitted.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2022 NGARCIA3 OUT TO CUSTOMER Completed