Permit Number: T22CM00267
Parcel: 11105153C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00267
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Completed
08/09/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00267 – DP21-301
3430 E Presidio Rd – Bldg 2. - R-2
New Building – Multi-Family (2nd Review)

TRANSMITTAL: August 9, 2022

This site is located in the R-2 zone (UDC 4.7.9). A multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Zoning has reviewed the building plan for compliance with DP21-0301 and although the plans appear to match Zoning cannot approve the building plan until the DP is approved.

2. Zoning acknowledges the approved DDO, T22SA00271. Provide a general note on the plan stating the DDO Case number, date of approval, what was modified and any conditions of approval, on the plan. The 9’-0” setback to the west property line shown on the DP does not meet the 10’-0” required perimeter yard setback, see UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
08/16/2022 JPEELDA1 FIRE REVIEW Reqs Change Plans show that you are installing a NFPA 13D Fire sprinkler and installing a fire alarm system. Occupancy is stated to be a R-3 then a fire alarm is not required. Please correct the plans.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033
Fire Plans Examiner
09/02/2022 SBLOOD1 ENGINEERING REVIEW Approved