Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00267
Parcel: 11105153C

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T22CM00267
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00267


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.

BUILDING REVIEW COMMENTS:
Denied
1. Provide clarification on the occupancy classification. R-2 occupancies are not permitted to be protected by an NFPA 13D system in accordance with Section 903.3.1.3. A one and two family dwelling is not an R-2 occupancy and thus would not be within the scope of the IBC. Provide clarification and correlate appropriate code requirements.
2. The allowable stories calculation is incorrect in accordance with Table 504.4. R-2 occupancies protected by NFPA 13D are not permitted.
3. The allowable square footage calculation is incorrect in accordance with Table 506.2. R-2 occupancies protected by NFPA 13D are not permitted.
4. The fire resistance rating of exterior walls is incorrect in accordance with Table 602.
5. Provide clarification of the existing walls that are adjacent with new building are compliant with Table 602. New construction is not permitted to make existing construction non-compliant.
6. The exterior wall type A is required to have a fire resistance rating of 1 hour in accordance with Table 602.
7. Windows 23 and 14 are required to emergency escape egress windows in compliance with Section 1030.
8. Provide occupant loads.
9. Provide a thorough egress plan.
10. The shared partition walls of the units are to be compliant with Section 420 of the IBC.
11. Additional comments may apply once comment #1 is addressed.

MECHANICAL REVIEW COMMENTS:
Denied
1. Clothes dryer exhausts exhausting more than 200 cfm is required to have makeup air. Provide clarification in accordance with Section 504.6.
2. Please provide a COMcheck that indicates compliance for new mechanical system and scan that data onto one of the mechanical sheets. This provides evidence the mechanical system is in compliance.

ELECTRICAL REVIEW COMMENTS
Denied
1. Please provide a prescriptive path or provide COMcheck calculations for the lighting. All mandatory requirements must be identified on the plans for compliance.
2. Provide a one line diagram.

PLUMBING REVIEW COMMENTS:
Approved
01/27/2022 ROBERT SHERRY WATER REVIEW Passed
02/03/2022 SSHIELD1 ENGINEERING REVIEW Needs Review
02/03/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
02/03/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00267 – DP21-301
3430 E Presidio Rd – Bldg 2. - R-2
Detached Garage Addition. (1st Review)

TRANSMITTAL: February 3, 2022

This site is located in the R-2 zone (UDC 4.7.9). A multi-family is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Zoning has reviewed the building plan for compliance with DP21-0301 and although the plans appear to match Zoning cannot approve the building plan until the DP is approved.

2. The 9’-0” setback to the west property line shown on the DP does not meet the 10’-0” required perimeter yard setback, see UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov
02/25/2022 JPEELDA1 FIRE REVIEW Reqs Change Denied
1. Provide clarification on the occupancy classification. R-2 occupancies are not permitted to be protected by an NFPA 13D system in accordance with Section 903.3.1.3. A one and two family dwelling is not an R-2 occupancy and thus would not be within the scope of the IBC. Provide clarification and correlate appropriate code requirements.
2. The allowable stories calculation is incorrect in accordance with Table 504.4. R-2 occupancies protected by NFPA 13D are not permitted.
3. The allowable square footage calculation is incorrect in accordance with Table 506.2. R-2 occupancies protected by NFPA 13D are not permitted.

Questions:
Jennifer Peel-Davis
Jennifer.Peel-Davis@Tucsonaz.gov
520-837-7033

Final Status

Task End Date Reviewer's Name Type of Review Description
02/25/2022 NGARCIA3 OUT TO CUSTOMER Completed