Review Status: Completed
Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Permit Number - T22CM00248
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/20/2022 | SBLOOD1 | ENGINEERING | REVIEW | Passed | |
| 01/25/2022 | IMONSHI1 | ZONING | REVIEW | Passed | |
| 02/16/2022 | SAFEBUILT | 2ND PARTY REVIEW | REVIEW | Reqs Change | Activity Number: T22CM00248 GENERAL: Provide written responses to all review comments. Provide a complete plan set. Provide additional documents as requested by review staff. STRUCTURAL REVIEW COMMENTS: Approved BUILDING REVIEW COMMENTS: Approved MECHANICAL REVIEW COMMENTS: Approved ELECTRICAL REVIEW COMMENTS Denied 1. 2018 IRC Section E3901.7 and E3902.3. Revise drawings with not less than one outdoor GFCI receptacle outlet that is readily accessible from grade level at the front and back of each dwelling unit. 2. 2018 IRC Section E3901.12 and E3902.3. Revise drawings with one outdoor GFCI receptacle outlet located on the same level and within 25 feet of the heating, air-conditioning and refrigeration equipment. PLUMBING REVIEW COMMENTS: Approved |