Permit Number: T22CM00248
Parcel: 136280760

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO

Permit Number - T22CM00248
Review Name: RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/25/2022 IMONSHI1 ZONING REVIEW Passed
02/16/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Reqs Change Activity Number: T22CM00248


GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Approved


ELECTRICAL REVIEW COMMENTS
Denied
1. 2018 IRC Section E3901.7 and E3902.3. Revise drawings with not less than one outdoor GFCI receptacle outlet that is readily accessible from grade level at the front and back of each dwelling unit.
2. 2018 IRC Section E3901.12 and E3902.3. Revise drawings with one outdoor GFCI receptacle outlet located on the same level and within 25 feet of the heating, air-conditioning and refrigeration equipment.


PLUMBING REVIEW COMMENTS:
Approved