02/01/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00215
Rooftop Solar Panels (1st Review)
5820 E HAWTHORNE ST

TRANSMITTAL DATE: ?February ?1, ?2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments

After looking at the google street view, it appears that the roof is sloped. Please reference the link below.
COMMENT: This plan set is not compliant with the Fire code. Demonstrate compliance with 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. Relocate the solar panels to provide a clear fire pathway on each roof plane per 2018 IFC 1204.2.1.1 and 1204.2.1.2.

https://www.google.com/maps/@32.2334547,-110.867889,3a,44.9y,207.22h,89.86t/data=!3m6!1e1!3m4!1sJKdpudv7GcJfQWHmM3DrNg!2e0!7i13312!8i6656

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by phone (520)837-4986 or email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.