Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2022 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
01/24/2022 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
01/24/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
01/24/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
02/01/2022 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
02/01/2022 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
02/01/2022 | SSHIELD1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
02/08/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1 . Provide a 25 or 30 amp branch circuit, disconnect, for the new insta hot water heater WH-1 and correlate with the panel schedule. See plumbing plan. 2. Provide compliance with the 2018 IECC for the lighting. 3. Show the location of the breaker panels on the power floor plans. Ref; 2018 IBC sec 107.1, 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements. |
02/25/2022 | JPEELDA1 | FIRE | REVIEW | Approved |