Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T22CM00208
Parcel: 12801005H

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00208
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Replacement of AC units constitutes new work so the submittal will require a heating/cooling load calculation to justify the capacities of the units being installed (Sections C403.3.1 and C403.2.2, IECC 2018). While ventilation calculations are not required, a test and balance report is required to verify that the total supply airflow and the outside airflow are at least equal to that which the previous AC unit provided.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2022 NGARCIA3 OUT TO CUSTOMER Completed