Permit Number: T22CM00178
Parcel: 134080610

Address:
8532 E CUIN PL

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00178
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/11/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00178
8532 E CUIN PL


TRANSMITTAL DATE: January 11, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve at this time. Please address the following comments

COMMENT: The gas pipe from the meter to the first Tee is undersized, based on a developed length of 45 ft the 1" will provide 284,000 BTU. From the meter to the first Tee is providing from both the Pool heater and the the BBQ Grill which combine give a total demand of 350 BTU.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2022 NGARCIA3 OUT TO CUSTOMER Completed