Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00127
Parcel: 13704155A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00127
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2022 SAFEBUILT 2ND PARTY REVIEW REVIEW Approv-Cond Activity Number: T22CM00127, T22CM0114, T22CM0128, T22CM0129, T22CM0130, T22CM0131, T22CM0132

GENERAL:
Provide written responses to all review comments.
Provide a complete plan set.
Provide additional documents as requested by review staff.


STRUCTURAL REVIEW COMMENTS:
Approved


BUILDING REVIEW COMMENTS:
Approved


MECHANICAL REVIEW COMMENTS:
Conditionally Approved
Approved/Subject to field approval


ELECTRICAL REVIEW COMMENTS
Conditionally Approved


PLUMBING REVIEW COMMENTS:
Conditionally Approved
Third Review:
1 thru 4 OK
5). OK-Fire main on P100 needs proper backflow protection. Tucson Amendment -IPC 608.17.4 ** see uploaded response sheet & ARS documentation** Field verify Backflow device compliance at time of inspection.
6 thru 16 OK


If you require additional clarification regarding these comments, please contact Doris Benoit at doris.benoit@tucsonaz.gov
04/20/2022 SSHIELD1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
04/22/2022 IMONSHI1 ENGINEERING REVIEW Approved
04/22/2022 STEVE SHIELDS ZONING REVIEW Approved