Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00112
Rooftop Solar Panels (1st Review)
244 E 24TH ST

TRANSMITTAL DATE: January 25, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments

COMMENT: After comparing the aerials to the plot plan it has come to my attention that there is a possible non-permitted porch addition on the South portion of the house the four panels located on roof #02. After researching PRO there were no records for the porch addition that could be verified or found. If no permits are available relocate the solar panel away from the porch structure or a permit must be obtained for the porch addition.

COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2022 VVERA1 OUT TO CUSTOMER Completed