Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T22CM00096
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2022 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 04/18/2022 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/20/2022 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the electrical plan review comments and provide a written response. 1. Please indicate what is ‘new’ and ‘existing to remain’ on the electrical power and lighting plans. 2. Provide complete electrical load calculations in the panel schedules and total load for the building. 3. Provide complete panel schedules include voltage, phase, load calculations, indicate “Main Breaker” or “Main Lug Only”. Include the sub-panel at the service location used to feed the Rear and Roof panels. 4. Provide an accurate electrical Meter Riser Diagram or Line Diagram for the service. If the electrical service is being upgraded or increased, provide a grounding detail and indicate all feeder conduit, conductor sizes and types. What is the 'Main Panel' ? 5. Provide for Tamper Resistant receptacle where applicable per NEC art 406.12. 6. Provide a complete electrical symbol legend. Ref; 2018 IBC section 107.1, 2017 NEC, City of Tucson Commercial Plan Submittal Requirements |
| 05/31/2022 | SSHIELD1 | ENGINEERING | REVIEW | Needs Review |