Permit Number: T22CM00095
Parcel: 126051360

Address:
4055 E 2ND ST

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00095
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2022 PCAMARE1 BUILDING-RESIDENTIAL REVIEW Completed
01/31/2022 STEVE SHIELDS ZONING REVIEW Reqs Change ZONING REVIEW TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT:
T22CM00095
4043 E 2nd St - R-1
Detached Shade Structure w/Solar. (1st Review)

TRANSMITTAL: January 31, 2022

This site is located in the R-1 zone (UDC 5.10.3). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

1. The site plan does not match the address on the application. The house shape does not match the current aerial photos and there are other structures on this site that need to be shown on the site plan.

2. Per the final plat for this parcel there is a 7’-6” easement that runs along the north end of the property. The proposed structure cannot encroach into this easement.

3. Provide a lot coverage calculation on the site plan that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf,

4. Per UDC Article 6.4.5.B.2 for structures like this the perimeter yard setbacks are measured from the post supporting the roof as long as there is no more than 2’ of roof overhang. Clearly show the post supporting the structure and provide the perimeter yard setbacks from the post to the property line.

If you have any questions about this transmittal, please contact Elisa Hamblin at Elisa.Hamblin@tucsonaz.gov.
01/31/2022 SSHIELD1 ENGINEERING REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/31/2022 VVERA1 OUT TO CUSTOMER Completed