Permit Number: T22CM00094
Parcel: 138081180

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00094
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2022 LSHAMIS1 ZONING REVIEW Reqs Change CDRC Transmittal

FROM: Loran Shamis
PDSD Zoning Review Section

PROJECT: T22CM00094
Detached Shade Structure with Solar (2nd Review)
766 W Calle Garcia

TRANSMITTAL DATE: February 18, 2022

DUE DATE: February 10, 2022

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


01. COMMENT: The following comments from the previous reviewer were not addressed.

02. COMMENT: Based on current aerial photos, there are two (2) detached accessory sheds located where you call out "(E) STRUCTURE (TYP.)" that appear some time after 2019. Zoning was not able to find an approved compliance review or permits for these structures. These structures do not appear to be meeting the 10' minimum side yard setback measured from the structure's adjacent exterior wall to the property line. If these structures are not meeting setbacks, the structures need to be moved to meet setbacks, removed, or a separate application the Design Development Option (DDO) can be used to reduce street yard setbacks - https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf.

03. COMMENT: Provide a lot coverage calculation on the site plan that meets the requirements of UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf

04. COMMENT: Provide the proposed setback dimensions. For structures like this the perimeter yard setbacks are measured from the post supporting the roof as long as there is no more than 2' of roof overhang. Clearly show the post supporting the structure and provide the perimeter yard setback from the post to the property line.

For questions regarding Zoning comments, please contact me at: Loran.Shamis@tucsonaz.gov
To resubmit your plans for additional review, please visit: https://docs.tucsonaz.gov/Forms/tucsonpermitapp