Permit Number: T22CM00084
Parcel: 11615190C

Address:
1835 W ANKLAM RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00084
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/18/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Building 2 (1835 W Anklam Rd)

Comment not resolved. Provide a detail showing how the shower compartment floor will be made impervious with a shower liner per Section 421.5.2, IPC 2018. [Initial comment: Provide details to show that the construction of the floor of the new shower complies with the requirements of Section 421.5, IPC 2018.]