Permit Number: T22CM00084
Parcel: 11615190C

Address:
1835 W ANKLAM RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T22CM00084
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2022 ELISA HAMBLIN ZONING REVIEW Passed
01/10/2022 EHAMBLI1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/11/2022 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
01/11/2022 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/11/2022 SBLOOD1 ENGINEERING REVIEW Passed
01/11/2022 ROBERT SHERRY WATER REVIEW Completed
01/11/2022 JPEELDA1 FIRE REVIEW Approved
01/12/2022 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Passed
01/12/2022 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Building 2 (1835 W Anklam Rd)
1. The water closet in room 203 is not shown in the floor plan but was not marked for removal in the demolition plan. Clarify the fate of the water closet.
2. Water supply piping is not existing for the new water closet in room 201. Show the size and source of the water supply to the new water closet.
3. Provide shower valves that comply with the requirements of Section 412.2, IPC 2018.
4. Provide details to show that the construction of the floor of the new shower complies with the requirements of Section 421.5, IPC 2018.
5. Specify the material of construction for the above and below ground sanitary drainage and vent pipes. Reference: Sections 702.1 and 702.2, IPC 2018.

Building 1 (1833 W Anklam Rd)
1. Provide shower valves that comply with the requirements of Section 412.2, IPC 2018.
2. Provide shower valves that comply with the requirements of Section 412.2, IPC 2018.
3. Specify the material of construction for the above and below ground sanitary drainage and vent pipes. Reference: Sections 702.1 and 702.2, IPC 2018.