Permit Number: T22CM00075
Parcel: 136210350

Address:
7473 E TAMARA DR

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T22CM00075
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/01/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00075
Rooftop Solar Panels (1st Review)
7473 E TAMARA DR

TRANSMITTAL DATE: ?February ?1, ?2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments

COMMENT: This plan set shows a roof slope of 10° degrees which is greater then 2-12 =9.46°. Demonstrate compliance with 2018 International Fire Code 1204.2.1.1. If the slope of the building is greater than 2:12 then compliance must be shown on the plans. Show a 36” wide access pathway from the eave to the ridge on both sides of the building. Relocate the solar panels to provide a clear fire pathway on each roof plane per 2018 IFC 1204.2.1.1 and 1204.2.1.2.


COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by phone (520)837-4986 or email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans