Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T22CM00075
Parcel: 136210350

Address:
7473 E TAMARA DR

Review Status: Completed

Review Details: OTHER

Permit Number - T22CM00075
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/25/2022 PCAMARE1 OIP REVIEW Reqs Change FROM: Paul Camarena
PDSD Residential Review Section

PROJECT: T22CM00075
Rooftop Solar Panels (1st Review)
7473 E TAMARA DR

TRANSMITTAL DATE: January 25, 2022



COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Residential Review Section comments were addressed.


COMMENT: Residential has reviewed the plan and cannot approve it at this time. Please address the following comments

COMMENT: The plan set that was submitted is for 8052 E Rosewood St.
Please provide the correct plan set.
COMMENT: Residential will review the application on the next submittal


If you have any questions about this transmittal, Contact Paul Camarena any time during the week by email Paul.camarena@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised Building Plans
.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2022 VVERA1 OUT TO CUSTOMER Completed